Fire stopping is the sealing of gaps and holes in fire-resisting walls and floors so that fire and smoke cannot spread through them. In a building split into flats or units, it decides whether a fire stays in the room where it started for the time the building was designed for, or gets into the next flat or the stairwell within minutes. This guide covers what fire stopping involves, where it usually fails in Croydon's mix of converted houses, purpose-built blocks and commercial premises, and what good work looks like.

Published 14 November 2026

What fire stopping actually does

Buildings with more than one occupancy are divided into fire compartments. Each flat, the communal stair, riser cupboards and plant rooms are separated by walls and floors built to resist fire for a set time, usually 30 or 60 minutes. That only works if the separating construction has no holes in it.

The trouble is that every building gets holes. Pipes, cables, ducts and soil stacks all pass through compartment walls and floors. Fire stopping seals around these service penetrations with tested products, so the wall or floor keeps the fire resistance it was designed for. It sits alongside fire doors and cavity barriers as part of the building's passive fire protection.

Where it most often goes wrong

Most fire stopping problems are not original construction faults. They come from later work by trades who cut through a fire-rated wall to run a new cable or pipe, then fill the hole with ordinary foam, or leave it open. We regularly find the same weak spots:

Does your building need it?

If you own, let or manage a building with more than one flat or unit, fire stopping is not optional. Compartmentation is required under the Building Regulations when the building is built or altered, and the responsible person must keep it in working order under fire safety law. Fire risk assessors now look for it routinely, and gaps in risers and voids are among the most common findings in their reports.

For a homeowner in a single house, the picture is different. Fire stopping matters most where your home joins another, such as a flat, a maisonette, or a garage that connects to the house. If you live in a flat, the sealing in your walls and floors protects your neighbours as much as you, and in a block it is usually the freeholder or managing agent who is responsible for it.

What good fire stopping looks like

There is no single product that suits every hole. The right solution depends on the size of the gap, what the wall or floor is made of, and what passes through it. Typical tested products include intumescent mastics for small gaps around cables and metal pipes, fire collars or wraps for plastic pipes, coated batt systems for larger openings with mixed services, and intumescent pillows where cables are likely to change.

The key point is that each product must be installed exactly as it was tested and to the manufacturer's instructions. A correct product fitted the wrong way can fail as badly as no product at all. Good work is also labelled where practical and photographed before any boxing or ceiling goes back, because once covered it cannot easily be checked.

How long it takes depends on access and condition. Sealing one riser cupboard can be a few hours. A survey and remedial programme across the risers and corridors of a whole block may run over several days or weeks, and it is often sensible to combine it with a fire door inspection so that all the communal fire protection is checked in one visit.

Records you should get afterwards

Whoever does the work should give you written records: what was sealed, where, which product and system was used, and photographs of each penetration. For landlords and managing agents, this is the evidence you will need for your fire risk assessor, your insurer or a future buyer. If a contractor cannot tell you what system they used, treat that as a warning sign.

Questions

Asked and answered.

Can I use expanding foam to seal gaps around pipes?

Only if it is a fire-rated foam tested for that gap size, wall type and service, and installed to the manufacturer's instructions. General-purpose foam from a builders' merchant gives no fire resistance and is one of the most common faults found in surveys.

How do I know if the fire stopping in my block is adequate?

Your fire risk assessment should flag visible problems in risers, cupboards and accessible voids. Where it does, or where works have been done without records, a specialist survey of the compartment lines will show what needs sealing and to what standard.

Is fire stopping the same as cavity barriers?

No, though they work together. Fire stopping seals holes where services pass through walls and floors, while cavity barriers close hidden voids, such as the gap behind cladding, so fire cannot travel through them.

Related

More from M&K.

Get In Touch

Talk to us about your fire doors.

Tell us what you've got, whether a single door, a block of flats or a commercial building, and we'll arrange a survey and give you a straight, written quote.

CallSpeak to Tony directly
WhatsAppMessage usSend photos of the job
  • Monday to Friday7:30 to 17:30
  • SaturdayBy arrangement
  • CoverageCroydon & the South East

Request a survey

Tell us about the doors or the building and we'll come back to you with a straight answer.

Or call or WhatsApp, whichever suits.